Products Topics Introduction Contact us

Home > Products > Digital Indicator > Accessories > Z961 / Z964

Accessories for measuring instrumentaions

Zener barrier Z961 / Z964

Zener barrier Z961/Z964
Feature
  • Safety barrier for load cell to be used for intrinsic safety explosion proof weighing system.
    Meets the intrinsic safety explosion proof requirement of Technology Institution of Industrial safety in Japan.
Specifications
Parts No. Z961 Z964
Rated voltage DC/AC6.5 V DC/AC10.0 V
Leakage currect 10 A 10 A
Zener rated voltage 8.1 V 11.7 V
Internal rated fuse 100 mA 50 mA
Max. voltage of circuit 17.4 V 24.8 V
Max. current of circuit 178 mA 25.3 mA
Min. resistance value
for limited current
98 980
Operatinal temp. humidity range -20 ~ 50 , 90 %RH or less (Non condensing) -20 ~ 50 , 90 %RH or less (Non condensing)
Permissible temp. humidity range -40 ~ 80 , 95 %RH or less (Non condensing) -40 ~ 80 , 95 %RH or less (Non condensing)
Weight Approx. 142 g Approx. 142 g
Plan
Wiring diaphragm
Download
CAD files (DXF) Specification sheet (PDF) ---
Z961/Z964 (30KB) Z961 : No.EN3538910 (50KB)
Z964 : No.EN3538911 (53KB)
---
Adobe Acrobat Reader is required to refer the Specification data sheet.
Acrobat Reader is a registered trademark of Adobe Systems Ltd.
The download of Adobe Acrobat Reader is here.